← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Ochsner AIR 80 C13A

Model code: 288600
Air Source (ASHP)CommercialHeating and Cooling
Heating capacity
83 kW
SCOP
3.56
W35
COP
3.75
A7/W35
Max flow temp
65°C
Sound power
78 dB(A)
Refrigerant
R410A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating and Cooling
Heating performance
Heating capacity83 kW
Max heating output (low temp)53.87 kW at A-7/W35
COP (heating)3.75 at A7/W35
SCOP (heating)3.56 at W35
Operating range (air)-22 to 40 °C
Heating flow temperatureup to 65 °C
Cooling performance
Cooling capacity66.8 kW
Max cooling output (high temp)61.7 kW at A30/W7
EER (cooling)3.2 at A30/W18
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level78 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1277 × 2965 × 1288 mm
Operational Weight348 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.