← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Oilon ChillHeat S

Model code: S 600
Water Source (WSHP)CommercialHeating & cooling
Heating capacity
740 kW
COP
4.2
W0/W35
Max flow temp
67°C
Refrigerant
R134A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR134A
ModeHeating & cooling
Heating performance
Heating capacity740 kW
Max heating output (low temp)638 kW at W0/W35
COP (heating)4.2 at W0/W35
Heating flow temperatureup to 67 °C
Cooling performance
Cooling capacity729 kW
Max cooling output (high temp)729 kW at W42/W7
EER (cooling)3.6 at W42/W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Dimensions (H×W×D)2071 × 4246 × 1005 mm
Operational Weight3700 kg