Product data sheetheatpumpdatabase.com

Panasonic ECOi-W AQV 125 H
Model code: P-AQVE0125HA
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
134 kW
SCOP
3.47
Not stated
COP
3.28
A7/W45
Max flow temp
55°C
Sound power
88 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 134 kW |
| Max heating output (low temp) | 134 kW at A7/W45 |
| COP (heating) | 3.28 at A7/W45 |
| SCOP (heating) | 3.47 at Not stated |
| Operating range (air) | -18 to 47 °C |
| Heating flow temperature | 18–55 °C |
| Cooling performance | |
| Cooling capacity | 115.8 kW |
| Max cooling output (high temp) | 115.8 kW at A35/W7 |
| EER (cooling) | 2.77 at A35/W7 |
| SEER (cooling) | 4.33 at Not stated |
| Cooling flow temperature | 7–18 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 88 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2185 × 1095 × 3155 mm |
| Operational Weight | 1227 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.