Product data sheetheatpumpdatabase.com

Panasonic ECOi-W VL 1104 H STD
Model code: P-VLE1104HA
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
302.1 kW
SCOP
3.3
Not stated
COP
3.02
A7/W45
Max flow temp
50°C
Sound power
95 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 302.1 kW |
| Max heating output (low temp) | 302.1 kW at A7/W45 |
| COP (heating) | 3.02 at A7/W45 |
| SCOP (heating) | 3.3 at Not stated |
| Operating range (air) | -18 to 49 °C |
| Heating flow temperature | 30–50 °C |
| Cooling performance | |
| Cooling capacity | 273.1 kW |
| Max cooling output (high temp) | 273.1 kW at A35/W7 |
| EER (cooling) | 2.74 at A35/W7 |
| SEER (cooling) | 3.53 at Not stated |
| Cooling flow temperature | 6–15 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 95 dB(A) (Sound Power LW(A)) |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.