← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Rhoss FullFLOW ECO DX TOHVTE 1280

Water Source (WSHP)CommercialHeating only
Heating capacity
335 kW
SCOP
4.37
W55
COP
4.3
W10/W45
Max flow temp
45°C
Sound power
96.5 dB(A)
Refrigerant
R1234ze

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR1234ze
ModeHeating only
Heating performance
Heating capacity335 kW
COP (heating)4.3 at W10/W45
SCOP (heating)4.37 at W55
Heating flow temperatureup to 45 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level96.5 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1780 × 1040 × 3550 mm
Operational Weight1735 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.