Product data sheetheatpumpdatabase.com

Rhoss POKER-P THAETP 250
Air Source (ASHP)CommercialHeating and Cooling
Heating capacity
47.4 kW
SCOP
3.83
W35
COP
3.2
A7/W45
Max flow temp
75°C
Refrigerant
R290
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating and Cooling |
| Heating performance | |
| Heating capacity | 47.4 kW |
| COP (heating) | 3.2 at A7/W45 |
| SCOP (heating) | 3.83 at W35 |
| Heating flow temperature | up to 75 °C |
| Cooling performance | |
| Cooling capacity | 44.8–44.8 kW |
| EER (cooling) | 2.81 at A35/W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Dimensions (H×W×D) | 2335 × 1224 × 1320 mm |
| Operational Weight | 685 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.