← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Rhoss WinPACK SE THAESY 2140

Air Source (ASHP)CommercialHeating and Cooling
Heating capacity
135.7 kW
SCOP
3.71
W35
COP
3.1
A7/W45
Max flow temp
45°C
Refrigerant
R410A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating and Cooling
Heating performance
Heating capacity135.7 kW
COP (heating)3.1 at A7/W45
SCOP (heating)3.71 at W35
Heating flow temperatureup to 45 °C
Cooling performance
Cooling capacity117.5–117.5 kW
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Dimensions (H×W×D)2440 × 2650 × 1350 mm
Operational Weight1320 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.