Product data sheetheatpumpdatabase.com
Rinnai HPMAX
Model code: HPMAX 06105
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
102.47 kW
SCOP
3.58
W35
COP
4.05
A7/W35
Max flow temp
60°C
Sound power
85 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 102.47 kW |
| Max heating output (low temp) | 97.13 kW at A7/W45 |
| COP (heating) | 4.05 at A7/W35 |
| SCOP (heating) | 3.58 at W35 |
| Operating range (air) | from -25 °C |
| Heating flow temperature | up to 60 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 85 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2010 × 2250 × 1450 mm |
| Operational Weight | 1105 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.