Product data sheetheatpumpdatabase.com

Shenling Polestar INV Series
Model code: LSQRF150PLV
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
160 kW
COP
3.42
A7/W45
Max flow temp
55°C
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 160 kW |
| Max heating output (low temp) | 160 kW at A7/W45 |
| COP (heating) | 3.42 at A7/W45 |
| Operating range (air) | -26 to 30 °C |
| Heating flow temperature | 30–55 °C |
| Cooling performance | |
| Cooling capacity | 150 kW |
| Max cooling output (high temp) | 150 kW at A35/W7 |
| EER (cooling) | 3.3 at A35/W7 |
| Cooling flow temperature | 5–20 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Dimensions (H×W×D) | 2300 × 2200 × 1150 mm |
| Operational Weight | 930 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.