Product data sheetheatpumpdatabase.com

SPRSUN R410A Icefield-M Series
Model code: CGK-080V2
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
11.96–26 kW
COP
4.52
A7/W35
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 11.96–26 kW |
| Max heating output (low temp) | 24.4 kW at A7/W45 |
| COP (heating) | 4.52 at A7/W35 |
| Cooling performance | |
| Cooling capacity | 23.2 kW |
| Max cooling output (high temp) | 18.33 kW at A35/W7 |
| EER (cooling) | 2.63 at A35/W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Dimensions (H×W×D) | 1410 × 1237 × 480 mm |
| Operational Weight | 200 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.