Product data sheetheatpumpdatabase.com

Swegon BETA Rev RFE SLN
Model code: BETA Rev RFE SLN /HP 16.4
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
171 kW
SCOP
3.2
W35
COP
3.32
A7/W45
Max flow temp
55°C
Sound power
89 dB(A)
Refrigerant
R513A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R513A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 171 kW |
| Max heating output (low temp) | 171 kW at A7/W45 |
| COP (heating) | 3.32 at A7/W45 |
| SCOP (heating) | 3.2 at W35 |
| Heating flow temperature | 28–55 °C |
| Cooling performance | |
| Cooling capacity | 162.5 kW |
| Max cooling output (high temp) | 162.5 kW at A35/W7 |
| EER (cooling) | 2.73 at A35/W7 |
| SEER (cooling) | 2.9 at W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 89 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2150 × 4200 × 1100 mm |
| Operational Weight | 1755 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.