← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Swegon EPSILON Echos

Model code: EPSILON Echos /HP 37
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
38 kW
SCOP
3.26
W35
COP
3.15
A7/W45
Max flow temp
50°C
Sound power
77 dB(A)
Refrigerant
R410A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating & cooling
Heating performance
Heating capacity38 kW
Max heating output (low temp)38 kW at A7/W45
COP (heating)3.15 at A7/W45
SCOP (heating)3.26 at W35
Heating flow temperature30–50 °C
Cooling performance
Cooling capacity35.3 kW
Max cooling output (high temp)35.3 kW at A35/W7
EER (cooling)2.85 at A35/W7
SEER (cooling)3 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level77 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1585 × 1305 × 695 mm
Operational Weight326 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.