← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Swegon OMICRON Sky S4 R5 HE

Model code: OMICRON Sky S4 R5 HE 43.4
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
424 kW
SCOP
3.75
W35
COP
3.29
A7/W45
Sound power
96 dB(A)
Refrigerant
R454B

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR454B
ModeHeating & cooling
Heating performance
Heating capacity424 kW
Max heating output (low temp)424 kW at A7/W45
COP (heating)3.29 at A7/W45
SCOP (heating)3.75 at W35
Cooling performance
Cooling capacity414 kW
Max cooling output (high temp)414 kW at A35/W7
EER (cooling)3.09 at A35/W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level96 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2443 × 5002 × 2256 mm
Operational Weight4100 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.