← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Swegon OMICRON Sky S4 R5 HE

Model code: OMICRON Sky S4 R5 HE 25.4
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
249 kW
SCOP
3.72
W35
COP
3.29
A7/W45
Max flow temp
60°C
Sound power
90 dB(A)
Refrigerant
R454B

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR454B
ModeHeating & cooling
Heating performance
Heating capacity249 kW
Max heating output (low temp)249 kW at A7/W45
COP (heating)3.29 at A7/W45
SCOP (heating)3.72 at W35
Heating flow temperatureup to 60 °C
Cooling performance
Cooling capacity245 kW
Max cooling output (high temp)245 kW at A35/W7
EER (cooling)3.34 at A35/W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level90 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2443 × 5002 × 2256 mm
Operational Weight3500 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.