← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Swegon SIGMA Zero Hi OH

Model code: SIGMA Zero Hi OH 250
Water Source (WSHP)CommercialHeating only
Heating capacity
246.3 kW
SCOP
5.43
W35
COP
3.8
W10/W45
Max flow temp
75°C
Sound power
84 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR290
ModeHeating only
Heating performance
Heating capacity246.3 kW
Max heating output (low temp)246.3 kW at W7/W45
COP (heating)3.8 at W10/W45
SCOP (heating)5.43 at W35
Heating flow temperatureup to 75 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level84 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1750 × 1635 × 1130 mm
Operational Weight1170 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.