← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Swegon ZETA Sky Hi HP R7

Model code: ZETA Sky Hi HP R7 4.1
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
43.9 kW
SCOP
3.75
W35
COP
3.21
A7/W45
Max flow temp
60°C
Sound power
83 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity43.9 kW
Max heating output (low temp)43.9 kW at A7/W45
COP (heating)3.21 at A7/W45
SCOP (heating)3.75 at W35
Heating flow temperatureup to 60 °C
Cooling performance
Cooling capacity43 kW
Max cooling output (high temp)43 kW at A35/W7
EER (cooling)2.89 at A35/W7
SEER (cooling)4.38 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level83 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1788 × 2200 × 1000 mm
Operational Weight548 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.