Product data sheetheatpumpdatabase.com

Swegon ZETA Zero HP
Model code: ZETA Zero HP 5.2
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
54.7 kW
SCOP
3.24
W55
COP
3.4
A7/W45
Max flow temp
60°C
Sound power
83 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 54.7 kW |
| Max heating output (low temp) | 54.7 kW at A7/W45 |
| COP (heating) | 3.4 at A7/W45 |
| SCOP (heating) | 3.24 at W55 |
| Heating flow temperature | up to 60 °C |
| Cooling performance | |
| Cooling capacity | 51 kW |
| Max cooling output (high temp) | 51 kW at A35/W7 |
| EER (cooling) | 3.11 at A35/W7 |
| SEER (cooling) | 3.82 at W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 83 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2136 × 2660 × 1130 mm |
| Operational Weight | 1170 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.