← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Toshiba Estia R32

Model code: HWT-1401HW-E
✓ BUS eligible✓ MCS listedAir Source (ASHP)ResidentialHeating & cooling
Heating capacity
2.44–18.39 kW
SCOP
4.65
W35
COP
4.6
A7/W35
Max flow temp
65°C
Sound power
69 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

✓ BUS eligible

Listed on the Ofgem BUS Product Eligibility List (24 Sep 2026).

PEL certificate: 011-1W0607_02

Grant also needs an MCS-certified installer and a qualifying system design.

MCS certification

✓ MCS listed

Certificate: 011-1W0607_02

General
Heat pump typeAir Source (ASHP)
ApplicationResidential
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity2.44–18.39 kW
Max heating output (low temp)16.13 kW at A2/W35
COP (heating)4.6 at A7/W35
SCOP (heating)4.65 at W35
Operating range (air)-25 to 25 °C
Heating flow temperature20–65 °C
Cooling performance
Cooling capacity10 kW
Max cooling output (high temp)10 kW at A35/W7
EER (cooling)2.45 at A35/W7
Cooling flow temperature7–25 °C
Electrical, acoustic and physical
Electrical supply220-240V (Single Phase)
Sound power level69 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1050 × 1010 × 370 mm
Operational Weight88 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.