← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Trane City RTSF

Model code: RTSF 060 G
Water Source (WSHP)CommercialHeating & cooling
Heating capacity
223.5 kW
SCOP
4.7
W55
COP
4.4
W10/W35
Max flow temp
80°C
Sound power
93 dB(A)
Refrigerant
R1234ze

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR1234ze
ModeHeating & cooling
Heating performance
Heating capacity223.5 kW
Max heating output (low temp)223.5 kW at W7/W45
COP (heating)4.4 at W10/W35
SCOP (heating)4.7 at W55
Heating flow temperatureup to 80 °C
Cooling performance
Cooling capacity212 kW
Max cooling output (high temp)212 kW at W45/W7
EER (cooling)4.66 at W45/W7
SEER (cooling)6 at W7
Electrical, acoustic and physical
Power input50.8 kW
Electrical supply380-415V (Three Phase)
Sound power level93 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1940 × 900 × 2240 mm
Operational Weight1675 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.