← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Trane Conquest CXAX

Model code: CXAX 017 HE SN R454B
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
47.5 kW
SCOP
3.31
W35
COP
2.98
A7/W45
Max flow temp
60°C
Sound power
83 dB(A)
Refrigerant
R454B

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR454B
ModeHeating & cooling
Heating performance
Heating capacity47.5 kW
Max heating output (low temp)47.5 kW at A7/W45
COP (heating)2.98 at A7/W45
SCOP (heating)3.31 at W35
Operating range (air)from -15 °C
Heating flow temperatureup to 60 °C
Cooling performance
Cooling capacity44 kW
Max cooling output (high temp)44 kW at A35/W7
EER (cooling)2.75 at A35/W7
SEER (cooling)4.37 at W7
Electrical, acoustic and physical
Power input15.94 kW
Electrical supply380-415V (Three Phase)
Sound power level83 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1747 × 1285 × 2346 mm
Operational Weight564 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.