← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Trane Lift

Model code: Lift 101-P
Water Source (WSHP)CommercialHeating only
Heating capacity
24.7 kW
SCOP
4.22
W55
COP
3.44
W30/W65
Max flow temp
60°C
Sound power
75 dB(A)
Refrigerant
R134a

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR134a
ModeHeating only
Heating performance
Heating capacity24.7 kW
Max heating output (low temp)24.7 kW at W10/W55
COP (heating)3.44 at W30/W65
SCOP (heating)4.22 at W55
Heating flow temperatureup to 60 °C
Electrical, acoustic and physical
Power input7.18 kW
Electrical supply380-415V (Three Phase)
Sound power level75 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1520 × 680 × 1200 mm
Operational Weight371 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.