York AMICHI

Model code: YMPA130
Air Source (ASHP)CommercialHeating and Cooling
Heating capacity
132 kW
COP
2.75
A7/W45
Max flow temp
55°C
Sound power
85 dB(A)
Refrigerant
R410A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating and Cooling
Heating performance
Heating capacity132 kW
Max heating output (low temp)132 kW at A7/W45
COP (heating)2.75 at A7/W45
Operating range (air)-18 to 48 °C
Heating flow temperature25–55 °C
Cooling performance
Cooling capacity122 kW
Max cooling output (high temp)122 kW at A36/W7
EER (cooling)2.95 at A35/W7
SEER (cooling)4.42 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level85 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2440 × 1200 × 2240 mm
Operational Weight979 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.