← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

York AMICHI

Model code: YMPA160
Air Source (ASHP)CommercialHeating and Cooling
Heating capacity
161 kW
COP
3.08
A7/W45
Max flow temp
55°C
Sound power
87 dB(A)
Refrigerant
R410A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating and Cooling
Heating performance
Heating capacity161 kW
Max heating output (low temp)161 kW at A7/W45
COP (heating)3.08 at A7/W45
Operating range (air)-18 to 48 °C
Heating flow temperature25–55 °C
Cooling performance
Cooling capacity159 kW
Max cooling output (high temp)159 kW at A36/W7
EER (cooling)3.12 at A35/W7
SEER (cooling)4.24 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level87 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2500 × 3050 × 2240 mm
Operational Weight1922 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.