← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

York YHME

Model code: YHME0222HE
Air Source (ASHP)CommercialHeating and Cooling
Heating capacity
185.5 kW
COP
2.84
A7/W45
Max flow temp
55°C
Sound power
99 dB(A)
Refrigerant
R134a

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR134a
ModeHeating and Cooling
Heating performance
Heating capacity185.5 kW
Max heating output (low temp)185.5 kW at A7/W45
COP (heating)2.84 at A7/W45
Operating range (air)-15 to 46 °C
Heating flow temperature35–55 °C
Cooling performance
Cooling capacity209.5 kW
Max cooling output (high temp)209.5 kW at A35/W7
EER (cooling)2.98 at A35/W7
Cooling flow temperature5–15 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level99 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2450 × 1955 × 3230 mm
Operational Weight1760 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.