← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

York YLCS-HA

Model code: YLCS-HA0415
Water Source (WSHP)CommercialHeating and Cooling
Heating capacity
469 kW
COP
3.87
W7/W45
Max flow temp
60°C
Sound power
93 dB(A)
Refrigerant
R134a

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR134a
ModeHeating and Cooling
Heating performance
Heating capacity469 kW
Max heating output (low temp)469 kW at W7/W45
COP (heating)3.87 at W7/W45
Operating range (air)-4.5 to 15 °C
Heating flow temperatureup to 60 °C
Cooling performance
Cooling capacity383 kW
Max cooling output (high temp)383 kW at W45/W7
EER (cooling)3.58 at W45/W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level93 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2100 × 3244 × 900 mm
Operational Weight4030 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.