Product data sheetheatpumpdatabase.com

York YLCS-HA
Model code: YLCS-HA0415
Water Source (WSHP)CommercialHeating and Cooling
Heating capacity
469 kW
COP
3.87
W7/W45
Max flow temp
60°C
Sound power
93 dB(A)
Refrigerant
R134a
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Water Source (WSHP) |
| Application | Commercial |
| Refrigerant | R134a |
| Mode | Heating and Cooling |
| Heating performance | |
| Heating capacity | 469 kW |
| Max heating output (low temp) | 469 kW at W7/W45 |
| COP (heating) | 3.87 at W7/W45 |
| Operating range (air) | -4.5 to 15 °C |
| Heating flow temperature | up to 60 °C |
| Cooling performance | |
| Cooling capacity | 383 kW |
| Max cooling output (high temp) | 383 kW at W45/W7 |
| EER (cooling) | 3.58 at W45/W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 93 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2100 × 3244 × 900 mm |
| Operational Weight | 4030 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.