Product data sheetheatpumpdatabase.com

Carrier AquaSnap 61AQ
Model code: 61AQ 040P
Air Source (ASHP)CommercialHeating & cooling

Heating capacity
38 kW
SCOP
4.1
W35
COP
3.97
A7/W35
Max flow temp
75°C
Sound power
73 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 38 kW |
| Max heating output (low temp) | 38 kW at A7/W55 |
| COP (heating) | 3.97 at A7/W35 |
| SCOP (heating) | 4.1 at W35 |
| Operating range (air) | -25 to 50 °C |
| Heating flow temperature | 20–75 °C |
| Cooling performance | |
| Cooling capacity | 32 kW |
| Max cooling output (high temp) | 32 kW at A35/W7 |
| EER (cooling) | 2.47 at A35/W7 |
| SEER (cooling) | 4.31 at W7 |
| Electrical, acoustic and physical | |
| Power input | 9.57 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 73 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2045 × 1145 × 1815 mm |
| Operational Weight | 527 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.