Product data sheetheatpumpdatabase.com

Clivet Spinchiller4 Large Premium
Model code: WSAN-YSC4 260.8
Air Source (ASHP)CommercialHeating & cooling

Heating capacity
700 kW
COP
3.12
A7/W45
Max flow temp
55°C
Sound power
93 dB(A)
Refrigerant
R32
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R32 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 700 kW |
| Max heating output (low temp) | 700 kW at A7/W45 |
| COP (heating) | 3.12 at A7/W45 |
| Operating range (air) | from -15 °C |
| Heating flow temperature | up to 55 °C |
| Cooling performance | |
| Cooling capacity | 670 kW |
| Max cooling output (high temp) | 670 kW at A35/W7 |
| EER (cooling) | 2.82 at A35/W7 |
| SEER (cooling) | 4.56 at W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 93 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2520 × 8200 × 2250 mm |
| Operational Weight | 5856 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.