Product data sheetheatpumpdatabase.com

Daikin Altherma monobloc
Model code: EBLQ011CA3V3
✓ BUS eligibleAir Source (ASHP)ResidentialHeating & cooling
Heating capacity
11.2 kW
SCOP
4.28
W35
COP
4.61
A7/W35
Max flow temp
55°C
Sound power
64 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
✓ BUS eligible
Listed on the Ofgem BUS Product Eligibility List (24 Sep 2026).
PEL certificate: 011-1W0259_11
Grant also needs an MCS-certified installer and a qualifying system design.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Residential |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 11.2 kW |
| Max heating output (low temp) | 11.2 kW at A7/W35 |
| COP (heating) | 4.61 at A7/W35 |
| SCOP (heating) | 4.28 at W35 |
| Operating range (air) | from -25 °C |
| Heating flow temperature | 25–55 °C |
| Cooling performance | |
| Cooling capacity | 11.6 kW |
| Max cooling output (high temp) | 11.6 kW at A35/W7 |
| EER (cooling) | 2.28 at A35/W7 |
| Cooling flow temperature | 5–22 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 220-240V (Single Phase) |
| Sound power level | 64 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1348 × 1160 × 380 mm |
| Operational Weight | 157 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.