PHNIX has announced GreenTherm One, an R290 air-to-water heat pump that puts heating, cooling, hot water and thermal storage into a single outdoor unit. The Guangzhou manufacturer is pitching it at installers who want to cut time on site: it says a typical setup can be done in around an hour.
What’s different
Most monobloc installs still need indoor kit: a hot water cylinder, often a buffer, and the pipework to join them up. GreenTherm One moves the storage outdoors. A thermal store is built into the unit, so there’s no separate indoor cylinder and much less pipework to run.
- One outdoor unit for space heating, cooling and domestic hot water
- Built-in thermal store, so no indoor hot water tank is needed
- R290 (propane) refrigerant, with protection measures on the water circuit
- Aimed at both new builds and retrofits
How the hot water works
The tank holds heat, not drinking water. Mains water is heated as it passes through the unit, so hot water is produced on demand rather than kept in storage. PHNIX says this reduces the Legionella risk and that, under normal operation, no separate anti-Legionella cycle is needed.
Controls and energy management
GreenTherm One uses PHNIX’s “AI” control features:
- AI Full Inverter varies compressor output to match demand
- AI Smart Grid plans heating around time-of-use electricity prices
- AI PV Drive runs the heat pump alongside solar generation (needs the optional iDrive Box)
Key specifications
PHNIX has now published a full specification for the first model, PASRW020B-BP2-PS-D5, and it’s listed in the database.
- Heating: 6 kW nominal, modulating 1.5–7.5 kW at A7/W35 (1.4–7.0 kW at A7/W55)
- Efficiency: SCOP 5.1 at 35 °C and 3.85 at 55 °C, both A+++
- Cooling: up to 7.5 kW at A35/W18 and 6.0 kW at A35/W7
- Flow and range: water up to 75 °C; runs from −25 °C outdoors
- Refrigerant: 0.35 kg of R290
- Noise: 55 dB(A) sound power (EN 12102), 38 dB(A) at 1 m
- Size: 750 × 580 × 1,950 mm and 185 kg – a tall, floor-standing outdoor unit rather than a typical low monobloc
- Supply: single-phase 220–240 V, with a built-in circulation pump and 3/4″ connections
The 0.35 kg charge is very small for a 6 kW unit, which helps with R290 siting rules. PHNIX still hasn’t given the thermal store volume, a UK price or MCS status, and putting the store outdoors raises the question of standing losses in winter.
Read the full announcement on PHNIX →
GreenTherm One and PHNIX’s other R290 GreenTherm monoblocs are listed below, and every PHNIX model is on the PHNIX manufacturer page.