Nibe F1345
Specifications and technical data
Ground Source (GSHP)CommercialR407C30.72 kW
| Manufacturer | Nibe |
|---|---|
| Model | F1345 |
| Model code | F1345-30 |
| Heat pump type | Ground Source (GSHP) |
| Application | Commercial |
| Refrigerant | R407C |
| Mode | Heating & cooling |
| Heating capacity | 30.72 kW |
| COP | 4.44 at B0/W35 |
| SCOP | 4.7 at W55 |
| Operating range (air) | from -12 °C |
| Power input | 6.92 kW |
| Dimensions (H×W×D) | 1800 × 600 × 643 mm |
| Weight | 330 kg |
| Sound power level | 47 dB(A) (Sound power LWA EN12102 at B0/W35) |
| Data added | 2026-06-12 |
| Data source | NIBE installer manuals / technical data |
Notes
Large ground source heat pump with two compressors for heating and cooling-capable systems.
Part no. 065298. EN14511 B0/W35: capacity 30.72 kW, power input 6.92 kW, COP 4.44. Pdesignh 35°C 35 kW; SCOP average climate 35/55°C 4.7/3.6. Two refrigerant circuits, R407C fill 2.0 kg each. Max operating current 25.3 A; recommended fuse 30 A. Width/depth/height 600/643/1800 mm; required ceiling height 1950 mm.
○ Awaiting verification
✎ Suggest a correction to this data
Data is compiled from manufacturer sources and may contain errors or gaps. Always confirm specifications with the manufacturer before making decisions.
More from Nibe
F1345
GSHP · 23 kW · SCOP 4.8
F1345
GSHP · 39.94 kW · SCOP 4.8
F1345
GSHP · 59.22 kW · SCOP 4.6
F1355
GSHP · 4–28 kW · SCOP 5
F1355
GSHP · 6–43 kW · SCOP 5
F2050
ASHP · 2.65 kW · SCOP 5.08
F2050
ASHP · 4 kW · SCOP 4.59
F2050
ASHP · 5.36 kW · SCOP 4.87