CIAT DYNACIAT LG

Specifications and technical data

Water Source (WSHP)CommercialR410A38 kW
ManufacturerCIAT
ModelDYNACIAT LG
Model codeDYNACIAT LG 100
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating & cooling
Heating capacity38 kW
COP5.44 at W10/W35
SCOP5.24 at W35
EER (cooling)4.65
Flow temperature30–55 °C
Power input11.7 kW
Dimensions (H×W×D)901 × 1044 × 600 mm
Weight200 kg
Sound power level69 dB(A) (LwA standard unit, ISO 9614-1)
Data added2026-06-10
Data sourcemanufacturer

Notes

Water-source heat pump and water chiller for commercial heating and cooling applications, designed for indoor plant-room installation.

Heating COP uses HW1 condition: evaporator water 10/7°C, condenser water 30/35°C, EN14511-3:2022. SCOP uses 30/35°C EN14825 average climate. EER uses CW1 cooling condition 12/7°C evaporator and 30/35°C condenser. R410A charge 3.6 kg.

○ Awaiting verification

✎ Suggest a correction to this data

Data is compiled from manufacturer sources and may contain errors or gaps. Always confirm specifications with the manufacturer before making decisions.