Heat PumpDatabase

Thermonova DELTA

Specifications and technical data

Air Source (ASHP)CommercialR29045–341 kW
ManufacturerThermonova
ModelDELTA
Model codeDELTA-HP3
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating only
Heating capacity45–341 kW
COP (heating)3.95 at A7/W45
SCOP (heating)4.19 at W35
Operating range (air)-20 to 42 °C
Heating flow temperature35–70 °C
Dimensions (H×W×D)2586 × 7794 × 1540 mm
Weight3718 kg
Data added2026-07-02
Data sourceManufacturer Data Sheet

View manufacturer page →

Notes

Second-generation monobloc air source heat pump using R290 propane with high delta-T design. Maximum heating capacity 341 kW, sustaining 265 kW even at -5°C ambient. Flow temperatures up to 70°C for district heating and commercial buildings including domestic hot water. Distributed in the UK by SAV Systems.

R290 propane, GWP 0.02 (sometimes cited as 3). Nominal COP 3.95 at 7°C ambient, 45/30°C water. 265 kW at -5°C ambient. 400V/50Hz/3-phase. Designed for heating-first operation with large delta-T (~30°C) and low return temperatures to maximise SCOP.

Where to buy (UK)

UK SupplierPure Renewables

✓ Manually verified by Heat Pump Database

✎ Suggest a correction to this data

Data is compiled from manufacturer sources and may contain errors or gaps. Always confirm specifications with the manufacturer before making decisions.