Daikin EWYT-B (487 kW)
Specifications and technical data
Air Source (ASHP)CommercialR32487 kW
| Manufacturer | Daikin |
|---|---|
| Model | EWYT-B |
| Model code | EWYT490B-SS |
| Heat pump type | Air Source (ASHP) All Air Source heat pumps → |
| Application | Commercial All Commercial heat pumps → |
| Refrigerant | R32 All R32 heat pumps → |
| Mode | Heating & cooling |
| Heating capacity | 487 kW |
| COP (heating) | 2.92 at Not stated |
| SCOP (heating) | 3.37 at Not stated |
| Operating range (air) | -20 to 46 °C |
| Heating flow temperature | 20–60 °C |
| Electrical supply | 380-415V (Three Phase) |
| Cooling capacity | 434 kW |
| Cooling flow temperature | -13–20 °C |
| EER (cooling) | 2.54 at Not stated |
| SEER (cooling) | 4.23 at Not stated |
| Dimensions (H×W×D) | 1800 × 1195 × 5025 mm |
| Operational Weight | 3370 kg |
| Sound power level | 96.6 dB(A) (Sound Power LW(A)) |
| Data added | 2026-07-07T00:00:00 |
| Data source | Manufacturer Data Sheet |
| Verification | Verified by a human |
Check noise at a neighbour’s window (MCS 020 a) →
Daikin EWYT490~B-SS modular air-cooled chiller/heat pump, R32, 487kW nominal heating / 434kW cooling, scroll compressors.
Where to buy (UK)
| UK Supplier | The Heat Pump Warehouse |
|---|---|
| UK Supplier | Space Air |
| UK Supplier | City Plumbing |
| UK Supplier | The Underfloor Heating Store |
✎ Suggest a correction to this data
Data is compiled from manufacturer sources and may contain errors or gaps. Always confirm specifications with the manufacturer before making decisions.
Alternatives to consider
Three Air Source (ASHP) heat pumps from other manufacturers closest in capacity to this one.
ECOi-W AQUA-Z DC 460 H
Panasonic · P-AQADZ0460HA
- Capacity
- 482 kW
- SCOP
- 3.64 (Not stated)
- Sound power
- 96 dB(A)
- Refrigerant
- R32
WinPOWER ECO THAEQU 5490
Rhoss
- Capacity
- 480.4 kW
- SCOP
- 3.88 (W35)
- Refrigerant
- R454B
Spinchiller4 Premium
Clivet · WSAN-YSC4 185.5
- Capacity
- 500 kW
- SCOP
- 3.91 (W35)
- Sound power
- 91 dB(A)
- Refrigerant
- R32
More from Daikin
Altherma 3 H HT
ASHP · 10.17 kW · SCOP 4.51 · BUS eligible
Altherma 3 H HT
ASHP · 11.57 kW · SCOP 4.51 · BUS eligible
Altherma 3 H HT
ASHP · 12.11 kW · SCOP 4.51 · BUS eligible
Altherma 3 H HT
ASHP · 10.17 kW · SCOP 4.57 · BUS eligible
Altherma 3 H HT
ASHP · 11.57 kW · SCOP 4.57 · BUS eligible
Altherma 3 H HT
ASHP · 12.11 kW · SCOP 4.57 · BUS eligible
Altherma 3 H HT
ASHP · 10.17 kW · SCOP 4.51 · BUS eligible
Altherma 3 H HT
ASHP · 11.57 kW · SCOP 4.51 · BUS eligible
Other Air Source (ASHP) heat pumps
H-600 CO₂
ASHP · 300–600 kW
H-1200 CO₂
ASHP · 600–1200 kW
H-1800 CO₂
ASHP · 900–1800 kW
H-2600 CO₂
ASHP · 1500–3000 kW
NX-Q-G06
ASHP · 157.5 kW
NX-Q-G06
ASHP · 174.6 kW
Compare with other products
Open the interactive database →
The Daikin name and logo are trademarks of their respective owner and are used here for identification purposes only.